12.2.105 Fault Code 47 - Safety Reached, S4 - SQS
Cause
This warning is an indication that a safety function is in the Reached state.
Troubleshooting
For the safe stopping functions, the possible controlled stop has been executed and the STO(+SBC) or the SOS function is ac-
tive.
As a default, faults with the code 46 or 47 are not saved into the fault history of the AC drive. The drive application can change
the logging mode so that these faults are saved in the fault history. The Activity log can be used to see the activation and deacti-
vation history of the safety functions.
12.2.106 Fault Code 47 - Safety Reached, S5 - SSR
Cause
This warning is an indication that a safety function is in the Reached state.
Troubleshooting
For the safe monitoring functions, the related limit is being monitored.
As a default, faults with the code 46 or 47 are not saved into the fault history of the AC drive. The drive application can change
the logging mode so that these faults are saved in the fault history. The Activity log can be used to see the activation and deacti-
vation history of the safety functions.
12.2.107 Fault Code 47 - Safety Reached, S6 - SLS 1
Cause
This warning is an indication that a safety function is in the Reached state.
Troubleshooting
For the safe monitoring functions, the related limit is being monitored.
As a default, faults with the code 46 or 47 are not saved into the fault history of the AC drive. The drive application can change
the logging mode so that these faults are saved in the fault history. The Activity log can be used to see the activation and deacti-
vation history of the safety functions.
12.2.108 Fault Code 47 - Safety Reached, S7 - SLS 2
Cause
This warning is an indication that a safety function is in the Reached state.
Troubleshooting
For the safe monitoring functions, the related limit is being monitored.
As a default, faults with the code 46 or 47 are not saved into the fault history of the AC drive. The drive application can change
the logging mode so that these faults are saved in the fault history. The Activity log can be used to see the activation and deacti-
vation history of the safety functions.
12.2.109 Fault Code 47 - Safety Reached, S8 - SLS 3
Cause
This warning is an indication that a safety function is in the Reached state.
Troubleshooting
For the safe monitoring functions, the related limit is being monitored.
As a default, faults with the code 46 or 47 are not saved into the fault history of the AC drive. The drive application can change
the logging mode so that these faults are saved in the fault history. The Activity log can be used to see the activation and deacti-
vation history of the safety functions.
AQ319736045637en-000101 / DPD01798168 | Danfoss A/S © 2021.06
Fault Tracing
VACON® NXP Advanced Safety Options
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON OPTEA and is the answer not in the manual?

Danfoss VACON OPTEA Specifications

General IconGeneral
BrandDanfoss
ModelVACON OPTEA
CategoryDC Drives
LanguageEnglish

Related product manuals