6. DESCRIPTIONS FOR TROUBLESHOOTING
E?111 DMCNET packet receiver overflows
More than 2 packets are received within 1ms.
Return it to the dealer or original manufacturer for repairing.
Reconnect power and clear alarm.
E?185 DMCNET Bus hardware abnormal
DMCNET Bus hardware abnormal or loss of communication packet
Return it to the dealer or original manufacturer for repairing.
Reconnect power and clear alarm.
E?201 Initial error of DMCNET data
Initial error of DMCNET data
Return it to the dealer or original manufacturer for repairing.
Reconnect power and clear alarm.
E?235 Position command overflows
1.
When temporary register for the feedback position overflows;
2.
When the zero return is triggered, but the zero return procedure is not completed;
3.
When E?060 and E?062 occur.
Implement the zero return procedure.
Reconnect power and clear alarm.
E?245 Positioning overtime
Positioning overtime for the position mode .
Return it to the dealer or original manufacturer for repairing.
Exceeding software direct limit.
Whether the position exceeds the value of P5-09. Please set the limit according
to actual conditions; if the position doesn’t exceed the limit, please set the
maximum:2147483648.