5 Planning the installation
Installation and Operation Manual for RPI M50A
32
5.9 Connecting to a datalogger via
RS485
The inverter can be connected to a datalogger via
RS485, e.g. for monitoring, changing settings or soft-
ware updates.
To ensure the proper work of the data connection,
consider the following recommendation and instruc-
tions.
For a detailed description how to perform the activities
described in this section, see “6.7 Connecting commu-
nication port I (optional)”, p. 45.
When you connect a single inverter
The termination resistor has to be switched on.
When you connect multiple inverters within the
same PV system
On the last inverter in the chain, the termination
resistor has to be switched on.
If your datalogger has no internal termination re-
sistor, the termination resistor on the rst inverter
in the chain has to be switched on too.
To each inverter a different inverter ID has to be
applied. This is necessary, so that the datalogger
or the maintenance software can identify each
inverter in the chain.
The baud rate has to be the same on each in-
verter.
Cable and wire requirements
Twisted and shielded cables with 2 solid wires.
Cable diameter: 5 mm
Wire cross-section: 1 mm
2
The RS485 cables should lay with distance from
the AC cable and the DC cables to avoid interfer-
ences.