8.11 Max. Power (Maximum feed-in power)
Overview
This function should be set only when requested by country regulations, authorities or your grid
operator.
With this function you can limit the maximum active power to be fed into the grid.
Accessing the menu
Main menu > Install Settings > Max. Power
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the
main menu. Otherwise, repeatedly press the button
ESC
until the main
menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the buttons and to select Install Settings.
To con rm your selection, press the button
ENT
.
3. The menu is protected by password 5555. Use the buttons and
to set each digit.
To con rm a digit, press the button
ENT
.
AC Connection: 3P4W
EPO: Normal Close
Anti-islanding: ON
Max. Power: 50000VA
Return to Factory
4. Use the buttons and to select Max. Power. The current setting
is displayed behind the menu entry.
5. To start editing the parameter value, press the button
ENT
.
6. To change the parameter value, use the buttons and .
To con rm your selection, press the button
ENT
.
To cancel the action, press the button
ESC
.
Con gurable Parameters
Parameter Description Value range
Max. Power
Limits the maximum power to be fed into the grid.
0 .. 55000 VA
Default: according to the coun-
try regulations