8.8.4 Reconnection time
Overview
With this function you can de ne a reconnection time in case the inverter has disconnected from the grid
because of a grid voltage or grid frequency failure (see “8.8.2 Voltage protection”, p. 61 and “8.8.3 Frequency
protection”, p. 63). When the failure disappears, the inverter will wait for the set reconnection time before it
reconnects to the grid.
Accessing the menu
Main menu > Install Settings > Grid settings > Reconnect T
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the
main menu. Otherwise, repeatedly press the button
ESC
until the main
menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the buttons and to select Install Settings.
To con rm your selection, press the button
ENT
.
3. Type in the password you received from Delta Support. Use the buttons
and to set each digit.
To con rm a digit, press the button
ENT
.
Country
Insulation
4. Use the buttons and to select Grid settings.
To con rm your selection, press the button
ENT
.
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
5. Use the buttons and to select Reconnect T.
This subsection consists of only one parameter which can be directly
edited.
6. To start editing the parameter value, press the button
ENT
.
7. To change the parameter value, use the buttons and .
To con rm your setting, press the button
ENT
To cancel the action, press the button
ESC
.
Con gurable Parameters
Parameter Description
Reconnect T
Reconnection time
Do not change this setting without prior
consultation with Delta Solar Support.