8 Settings
Installation and Operation Manual for RPI M50A
62
Installation and Operation Manual for RPI M50A
62
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
5. Use the buttons and to select Voltage protection.
To con rm your selection, press the button
ENT
.
High On: 259.0V
High Off T: 0.3s
Low Off: 104.0V
High Off: 276.0V
6. If you need to change a parameter, use the buttons and to
select the parameter.
7. Press the button
ENT
to start editing the parameter value.
8. Use the buttons and to change the parameter value.
To con rm your setting, press the button
ENT
or press the button
ESC
to
cancel the action.
9. Repeat steps 6 to 8 for the other parameters if you need to change
them.
Con gurable Parameters
Parameter Description
High Off
Voltage High Off
High On
Voltage High On
High Off T
Disconnection time for Voltage High Off
Low Off
Voltage Low Off
Low On
Voltage Low On
Low Off T
Disconnection time for Voltage Low Off
Hi Off Slow
Voltage High Off Slow
Hi On Slow
Voltage High On Slow
Hi Off Slow T
Disconnection time for Voltage High Off Slow
Lo Off Slow
Voltage Low Off Slow
Lo On Slow
Voltage Low On Slow
Lo Off Slow T
Disconnection time for Voltage Low Off Slow
Table 8.1.: Con gurable parameters for Grid settings > Voltage Protection
Do not change this setting without prior
consultation with Delta Solar Support.