Installation and Operation Manual for RPI M50A
8 Settings
73
Installation and Operation Manual for RPI M50A
P(V)
Power vs. Frequency
Power Limit
5. Use the buttons and to select Power vs Frequency. The cur-
rent setting is displayed behind the menu entry.
F Recovery: 50.20Hz
Gradient: 100%
F Start: 50.20Hz
Mode: ON
6. To change the mode, use the buttons and and press the but-
ton
ENT
.
To switch the function on, select ON and press the button
ENT
.
To switch the function off, select OFF and press the button
ENT
. When
you switch the function off, you can ignore the following steps.
F Recovery: 50.20Hz
Gradient: 100%
F Start: 50.20Hz
Mode: ON
7. Use the buttons and to select a parameter and press the but-
ton
ENT
.
8. To change the parameter value, use the buttons and .
To con rm your setting, press the button
ENT
To cancel the action, press the button
ESC
.
9. Repeat steps 7 to 8 for all parameters you want to change.
Con gurable Parameters
Parameter Description
Mode
Switches the function on and off.
F Start
The grid frequency at which the inverter starts to limit the active power according to
the Gradient parameter.
F Recovery
The grid frequency at which the inverter reconnects to the grid or at which the
inverter feeds-in full power again. The behavior depends on the selected country and
grid.
Gradient
Adjustment of the active power fed into the grid in percent per Hz when the grid fre-
quency is between F Start and F Stop.
T Recovery When the grid frequency drops to F Recovery, the inverter will wait for the time
de ned in T Recovery before it returns to normal operating behavior.
Do not change this setting without prior
consultation with Delta Solar Support.