Installation and Operation Manual for RPI M50A
8 Settings
77
Installation and Operation Manual for RPI M50A
Q lower: Ind 1.00
P lower: 45%
Q upper: Ind 1.00
Mode: ON
6. To change the mode, use the buttons and to select Mode and
press the button
ENT
.
To switch the function on, select ON and press the button
ENT
.
To switch the function off, select OFF and press the button
ENT
. When
you switch the function off, you can ignore the following steps.
Q lower: Ind 1.00
P lower: 45%
Q upper: Ind 1.00
Mode: ON
7. If you need to change a parameter, use the buttons and to
select the parameter and press the button
ENT
.
8. To change the parameter value, use the buttons and .
To con rm your setting, press the button
ENT
.
To cancel the action, press the button
ESC
.
9. Repeat steps 7 to 8 for other parameters if you need to change them.
Con gurable Parameters
Parameter Description
Mode
Switches the function on and off.
Q upper
Sets up the upper limit for the reactive power which is set as a cos phi (cos φ).
P upper
Sets up the upper limit for the active power which is set in per cent of the nominal
power.
Q lower
Sets up the lower limit for the reactive power which is set as a cos phi (cos φ).
P lower
Sets up the lower limit for the active power which is set in per cent of the nominal
power.
V lock-in
The lower limit of the grid voltage range in which the function is active. The param-
eter is used for Italy only.
V lock-out
The upper limit of the grid voltage range in which the function is active. The param-
eter is used for Italy only.
Do not change this setting without prior
consultation with Delta Solar Support.