8 Settings
Installation and Operation Manual for RPI M50A
84
Installation and Operation Manual for RPI M50A
84
t1: 0.30s
Vdrop: 0%
Dead band: -10%
Mode: ON
4. To change the mode, use the buttons and to select Mode and
press the button
ENT
.
To switch the function on, select Mode = ON and press the button
ENT
.
To switch the function off, select select Mode = OFF and press the but-
ton
ENT
. When you switch the function off, you can ignore the following
steps.
t1: 0.30s
Vdrop: 0%
Dead band: -10%
Mode: ON
5. If you need to change a parameter, use the buttons and to
select the parameter and press the button
ENT
6. To change the parameter value, use the buttons and .
To con rm your setting, press the button
ENT
To cancel the action, press the button
ESC
.
7. Repeat steps 5 to 6 for all parameters you need to change.
Con gurable Parameters
Parameter Description
Mode
Switches the function on and off.
Dead band
Dead band
Vdrop
Drop voltage
t1
Time t1
U1
Voltage U1
t3
Time t3
K factor
K factor
Do not change this setting without prior
consultation with Delta Solar Support.