EasyManua.ls Logo

DencoHappel MATRIX OP71 - Page 58

Default Icon
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating MATRIX control panel OP71 MATRIX Control Panel OP71
58 PR-2009-0021-GB • Subject to modifications • R5-04/2016
8.6.16.2 Settings submenu
Entries of the functional parameters are made in the “settings” submenu:
to assign setpoint values for the economy mode
to set limits for supply-air temperature in the heating and cooling mode
to specify standby temperatures
For the air flush function
to select MA (mixed-air) damper position
to minimum outside-air rate
to minimum fan speed
Settings economy mode
The setpoint values that are valid during the economy mode (night operation) are ente-
red in the “economy mode” submenu.
Settings
Economy mode
Supply temperature limits
Basic reduced temperature
Air flush function
Economy mode
Room temperature
Supply air temperature
Fan mode
Controller mode
Central and decentralized air
handling units
Additionally for the central air handling
units, alternatively to the fan mode
Room temperature or
supply-air temperature·
Fan mode
Controller operating mode·
MA damper positionor
Outside-air volume flowor
Outside-air automatic
Secondary-air louveror
Louvre angle offset
Plant/fan ON/OFF
In combination with:
– Supply-air/extract-air duct pressureor
– Supply-air/extract-air volume flowor
– Fan speed
NOTICE!
If the function "Synchronize setpoint values" is activated on the MATRIX-control
panel OP71 (only adjustable with the MATRIX.PC service tool), the menu items
room temperature/inlet air temperature are not shown in the economy mode
submenu.

Table of Contents