EasyManua.ls Logo

DencoHappel MATRIX OP71 - Submenu Setting Supply-Air Duct Pressure And;Or Extract-Air Duct Pressure

Default Icon
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating MATRIX control panel OP71 MATRIX Control Panel OP71
52 PR-2009-0021-GB • Subject to modifications • R5-04/2016
The speed for the supply-air and/or the extract-air fan is set in percent of the maximum
speed. The maximum speed is determined by the configuration of the frequency con-
verter and the motor used.
In the delivery state ex works, this is the nominal speed of the motor (see vehicle iden-
tification plate of the motor).
Should the supply and exhaust air fan be operated at various speed, this can take
place by setting a factor or an offset. See also the in chapter <Name>Air handling unit
submenu the chapter "Central plant air handling unit Ü fans" on page 69.
8.6.7 Submenu setting "Supply-air duct pressure" and/or "Extract-air duct pressure"
The menus "Supply-air duct pressure" or "Extract-air duct pressure" appear in
combination with the menu "Plant/fan" and are only shown whenever they are
activated in the menu <Name>Menu enabling for ... (see page 86) and a fan speed set-
ting was selected with duct pressure (see in chapter <Name>Air handling unit subme-
nuthe chapter "central plant air handling unit Ü fans" on page 69). If no extract-air or
supply-air fan is available or if a slave control from the setting of a factor or offset was
selected, only one of the two menus appears.
The setting of the supply-air and/or extract-air duct pressure is shown absolutely in
Pascal. In order to avoid faulty entries, the minimum and maximum adjustable setpoint
can be changed with the MATRIX.PC service tool.
30 %
0 % 10 0 %
Fan speed
Value range: 0 to 100%
Adjustable steps: 1%
Factory setting: 10%
NOTICE!
The speed setting can be influenced by the minimum and maximum permis-
sible speed saved in the controller or the frequency converter. The values in the
controller can be changed with the help of the MATRIX.PC service soft-
ware.The values of the frequency converter can be changed using the control
panel of the power inverter.
Pa
Pa
Supply-air duct pressure
65
Extract-air duct pressure
72
Value range: 0 to 5,000 Pa (factory setting)
Adjustable steps: 1 Pa
Factory setting: 0 Pa
NOTICE!
The measuring range of the pressure sensor(s) is configured (e.g. 0-500
Pa) during commissioning using the MATRIX.PC service tool or the
MATRIX control panel OP71 (see chapter "Sensor inputs range start/range
end" on page 76). If this range is smaller than the adjustment range configu-
red for the control panel, then the measuring range of the pressure sensor
is automatically taken over as the adjustment range.

Table of Contents