Operating MATRIX control panel OP71 MATRIX Control Panel OP71
80 PR-2009-0021-GB • Subject to modifications • R5-04/2016
8.9.1 Week program submenu
In menu "1. week programme" entries are made:
– for enabling or disabling the week programme – see „Enabling menu options“
on page 43 for more details
–for deleting the week programme –see „Deleting settings“ on page 44 for more
details
–to carry out cluster assignment – see „Assigning clusters to programmes“ on
page 45 for more details
–for changing programme names – see „Changing programme names“ on
page 46 for more details
–for morning warmup time – the time frame in minutes is set here, when the initial
air treatment before the actual switching on of the time programme should start. The
initial air treatment takes place during switch over from economy to normal mode.
In this phase the mixing-air damper of the outside-air units remains closed.
– for the switching pattern for all weekdays
Monday - Friday
Saturday - Sunday
as well as on each single day of the week.
You can enter a maximum of four switching times for each day:
These switching times are entered either for
– All week days:
Switching times that are entered in the “all week days” menu option are valid for all
week days without further entries. They are automatically copied into all following
menu options of the clock timer. Previous entries are then overwritten. After entries
in the “all week days” menu option have been made it is possible to overwrite these
switching times by entries in the further clock timer menu options.
– Monday - Friday:
Switching times that are entered in the “Monday - Friday” menu option are valid bet-
ween Monday and Friday without further entries. They are automatically copied into
the following “Monday” to “Friday” clock timer menu options. Previous entries are
then overwritten.
1. Week programme
Activate
Delete programme
Cluster assignment
Change programme
Morning warmup time
Time in minutes
Value range: 5 to 60 minutes; factory setting: 10 min;
If "---" is set, the programme is disabled.
2 x switching into the “normal mode“ (day operation) and