125ECLYPSE APEX
Data Bus Shields: Twist
together and Isolate
with electrical tape
Typical BACnet 24VAC-
Powered Controller
Data Bus Shield:
Isolate with
Electrical Tape
Typical BACnet 24VAC-
Powered Controller
Data Bus: Shielded Twisted Pair Cable
NET+
NET-
NET+
NET-
Typical BACnet 24VAC-
Powered Controller
NET+
NET-
Data Bus Shield:
Isolate with
Electrical Tape
Typical BACnet Line-
Powered Controller
NET-
NET+
COM
Electrical
System
Ground
The shield of the data bus must be connected to
the electrical system ground at one point only
usually at the Building Controller, when present
RS-485
-
+
S
ECLYPSE
Data Bus Shields:
Twist Together
and Connect to
‘COM’ Terminal
Data Bus Shield
Connect to the ‘S’
terminal
Figure100: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data Bus Segment with an ECY
Series Controller located in the Middle of the Data Bus
Using Repeaters to Extend the Data Bus
A BACnet MS/TP data bus segment can be up to 1220 meters (4000 feet) long with up to a maximum
of 50 devices. When a greater length is required, a solution is to use a repeater. A repeater increases
the maximum length of the data bus.
Using a Repeater to Extend the Length of the BACnet MS/TP Data Bus
Repeaters can be used to extend a BACnet MS/TP data bus up to 3660 meters maximum total length.
Do not use more than two repeaters on a BACnet MS/TP LAN.
A BACnet MS/TP repeater is a bi-directional device that regenerates and strengthens the electrical
signals that pass through it. It creates two electrically-isolated BACnet MS/TP data bus segments that
transparently enable devices on one side of the repeater to communicate with any device on the other
side. The two BACnet MS/TP data bus segments have the same requirements of an ordinary BACnet
MS/TP data bus segment; that is, each BACnet MS/TP data bus segment:
£ Can be up to 1220 meters (4000 feet) long.
£ The first and last device on the data bus must have End-of-Line (EOL) termination resistors con-
nected across the two data lines/wires of the twisted pair.
£ Must respect the maximum limit for Device Loading.
£ Will have the same network number as they remain part of the same network or LAN.
It is recommended that you connect no more than 50 of our ⅛ or ½-load devices on all BACnet MS/TP
Data Bus repeater segments when a baud rate of 19 200 or higher is used (preferably 38 400 baud).
This is to ensure that the BACnet MS/TP Data Bus has enough bandwidth to efficiently communicate
network variables between controllers.
Do not use more than two repeaters on a BACnet MS/TP data bus.
A repeater can only connect two BACnet MS/TP data bus segments even if it has ports to support more than two
BACnet MS/TP data bus segments.
A repeater can be added anywhere to a data bus segment including the end of the segment as shown
below.
END
EOL ON
EOL Externally Set
ECLYPSE
Figure101: Using a Repeater to Extend the Range of the LAN
BACnet MS/TP Communication Data Bus Fundamentals

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECLYPSE APEX and is the answer not in the manual?

Distech Controls ECLYPSE APEX Specifications

General IconGeneral
BrandDistech Controls
ModelECLYPSE APEX
CategoryControl Systems
LanguageEnglish

Related product manuals