33ECY-303 Preloaded Applications
EconEnableBI (MSV5)
This variable is used to display the actual status of an economizer enable input configured on inputs
between UI1 to UI5.
ID Enumeration Default Value
Multi State Value 5
1 = Enable: The outside air dampers can be used to provide cooling to
the space.
2 = Disable: The outside air dampers cannot be used to provide cooling
to the space.
3 = Unconfig: This function is not configured
Unconfig
OccDetection (MSV6)
This variable is used to display the occupancy detection status. This variable is controlled based on
UI1Config to UI5Config. If one of these configurations are set to OccDetect, the associated input will
be used to connect an occupancy sensor. If an EC-Smart-Vue with the –M option is connected, the
motion detection will be used in parallel with the inputs to calculate the OccDetection.
ID Enumeration Default Value
Multi State Value 6
1 = Occupied: Motion is detected from the configured sensor.
2 = Unoccupied: Motion is not detected from the configured sensor.
3 = Unconfig: No motion sensor configured.
Unconfig
WindowContact (MSV7)
This variable is used to display the window contact status. This variable is controlled based on UI1-
Config to UI5Config. If one of these configurations is set to Window, the associated input will be used
to connect a window contact. When the window is open, the setpoints are forced to the unoccupied
setpoints.
ID Enumeration Default Value
Multi State Value 7
1 = Close: Window is close
2 = Open: Window is open
3 = Unconfig: No window contact configured.
Unconfig
EcoVueHeatStatus (MSV8)
This variable is used to display the ECO-Vue heating value of the system. The more energy efficient is
the end-user, the more leaves he will get on the ECO-Vue.
ID Enumeration Default Value
Multi State Value 8
1 = 1 Leaf: Low Energy Efficieny
2 = 2 Leaves: Med Energy Efficieny
3 = 3 Leaves: High Energy Efficieny
4 = 4 Leaves: Highest Energy Efficieny
N/A
EcoVueCoolStatus (MSV9)
This variable is used to display the ECO-Vue cooling value of the system. The more energy efficient is
the end-user, the more leaves he will get on the ECO-Vue.
ID Enumeration Default Value
Multi State Value 9
1 = 1 Leaf: Low Energy Efficieny
2 = 2 Leaves: Med Energy Efficieny
3 = 3 Leaves: High Energy Efficieny
4 = 4 Leaves: Highest Energy Efficieny
N/A
Variables