61ECY-303 Preloaded Applications
Fan and Equipment Delays
From this subsection the delays for fans and equipment can be configured.
Parameter Description
Occupied Fan Start Delay
Input the delay in seconds before allowing the fan to start after the system have been
set to occupied.
Fan Stop Delay
Input the delay in seconds before stopping the fan. This delay is used to dissipate the
heat from the electric heater.
Enable Equipment Delay
Input the delay in seconds before enabling the outputs after the fan status have been
verified.
Change Over Delay (Heat/Cool) Input the minimum delay in minutes between heating/cooling.
Bypass Mode Override Time
Enter the bypass delay in minutes when the room occupancy is overridden either via
the EC-Sensor-SO, the EC-Smart-Comfort or the EC-Smart-Vue.
Fan Control Mode
Indicate the fan control mode based on the OccupancyStatus.
On
– When in Unoccupied, Bypass or Standby mode, the fan is controlled based on the
terminal load like in Auto mode.
Auto
– The fan start is controlled based on the terminal load.
Off
– The fan is always set to Off.
Initial Start Delay Enter delay in seconds before enabling the controller after a reboot.
Outputs Assignment
The Output Assignment tab indicates which physical outputs are assigned to the configured outputs
based on the Outputs Configuration in the Hardware Configuration tab. This facilitates output wiring.
Configuring the Preloaded Applications