29ECY-303 Preloaded Applications
ID Units Valid Range Default Value
Binary Value 3 On/Off On to Off Off
Cool4 (BV4)
This variable is used to display the actual cooling stage 4 output value. When the system is configured
in heat pump mode, this output represents the compressor stage 4 output.
ID Units Valid Range Default Value
Binary Value 4 On/Off On to Off Off
Heat1 (BV5)
This variable is used to display the actual heating stage 1 output value.
ID Units Valid Range Default Value
Binary Value 5 On/Off On to Off Off
Heat2 (BV6)
This variable is used to display the actual heating stage 2 output value.
ID Units Valid Range Default Value
Binary Value 6 On/Off On to Off Off
Heat3 (BV7)
This variable is used to display the actual heating stage 3 output value.
ID Units Valid Range Default Value
Binary Value 7 On/Off On to Off Off
MinPosEnable (BV8)
This variable is used to control the output used for the minimum damper position.
ID Units Valid Range Default Value
Binary Value 8 On/Off On to Off Off
ReversingValve (BV9)
This variable is used to control the output used for the reversing valve.
ID Units Valid Range Default Value
Binary Value 9 On/Off On to Off Off
PowerExhaust (BV10)
This variable is used to control the output used for the power exhaust.
ID Units Valid Range Default Value
Binary Value 10 On/Off On to Off Off
OptStartEnableUpdate (BV11)
This variable is used to configure if the optimum start can automaticaly update OptStartCoolFac-
tor(AV14) and/or OptStartHeatFactor(AV15).
Variables