74 ECY-303 Preloaded Applications
£ Press and hold the Menu button for 5 seconds.
End-User Overrides
From the Allure EC-Smart-Vue’s Overrides submenu, the controller’s outputs can be overridden.
Output overrides range from 0 – 100% in increments of 1%.
For digital outputs, any value different from 0 represents On.
To enter the advanced menus:
1. Hold the Menu button for five seconds:
°F
pm
5 sec
The password field appears.
2. Use the arrow keys to increase or decrease the displayed number until it matches the configured
password.
Screen timeout: 15 s
By default, the password is 9995.
3. Press the Menu button to submit the password.
Screen timeout: 15 s
Upon submitting the correct password, the advanced menu is displayed.
4. Press the Menu button several times until OVR appears on the display.
Press several times
5. Use either of the arrow keys to enter the Overrides submenu.
Screen timeout: 30 s
Allure EC-Smart-Vue Screen-by-Screen Guide