72 ECY-303 Preloaded Applications
Output Configuration Tables
Output (BACnet object Default Valid Choices Parameter Description
COOLHEAT STGS (MSV 32)
1
Cool Cooling stages
x 2
3
4
1
Heat Heating stagesx 2
3
REV VLV (MSV 33)
x 1 Unconfig
Reversing valve is
unconfigured
2 Cooling Reversing valve cooling
3 Heating Reversing valve heating
PROP HT (MSV 34)
x 1 Unconfig
Proportional heating is
unconfigured
2 Analog 0-10V 0 – 10 V analog signal
3 Analog 2-10V 2 – 10 V analog signal
4 PWM Pulse width modulation
DAMPERS (MSV 35)
x 1 Unconfig Dampers are unconfigured
2 Analog 0-10V 0 – 10 V analog signal
3 Analog 2-10V 2 – 10 V analog signal
4 Analog 0-10V PE
0 – 10 V protected earth
analog signal
5 Analog 2-10V PE
2 – 10 V protected earth
analog signal
6 EconEnable Economizer enabled
7 Econ & MinPos
Economizer & minimum
damper position
8 Min Pos Enable
Enable minimum damper
position
HUMIDIFIER (MSV 36)
x 1 Unconfig Humidifier is unconfigured
2 Analog 0-10V 0 – 10 V analog signal
3 Analog 2-10V 2 – 10 V analog signal
4 PWM Pulse width modulation
5 Digital Digital signal
ENABLE
x 1 Enable Enable output control
2 Disable Disable output control
Viewing the Wiring Guide
From the Allure EC-Smart-Vue’s Wiring submenu, the correct wiring options can be viewed. Once the
Output Configuration is set, the Wiring submenu will indicate what needs to be wired to a particular
output number on the controller.
To enter the advanced menus:
1. Hold the Menu button for five seconds:
The password field appears.
2. Use the arrow keys to increase or decrease the displayed number until it matches the configured
password.
Allure EC-Smart-Vue Screen-by-Screen Guide