58 ECY-303 Preloaded Applications
Parameter Description
Discharge Low Limit Setpoint
Used to calculate the Actual Low Limit Alarm. When the fan is running and the discharge
temperature is lower than this value, the low limit alarm is set to alarm mode.
Actual Low Limit Alarm Used to indicate if the system is in low limit alarm mode.
Low Limit Reset Type Used to reset the LowLimitAlarm variable and restart the unit.
Humidification Parameters
Within this subsection, the
Humidification Parameters
can be set.
Parameter Description
Space or Return Humidity Setpoint Enter the setpoint for the desired space or return humidity.
Discharge Humidity High Limit Enter the upper limit for the discharge humidity.
Space or Return Dehumidification
Setpoint
Enter the setpoint for the desired space or return dehumidification used to control the
cooling stages.
Enable Dehumidification Enable or disable dehumidification.
Compressor and Cooling Parameters
Compressor and Cooling Parameters can be configured from this subsection.
Configuring the Preloaded Applications