3. WP8010 INSTALLATION
D-306233 CUSDOC PM-10/30 V18 DSC TRIPLE EN INST 83
WP8010
WP8030
Caution! Risk of explosion if battery is
replaced by an incorrect type. Dispose of
used batteries according to the
manufacturer's instructions.
Note: For compliance with CE standards the
battery capacity must be at least 1300 mAh.
(1) The external devices must be connected
between 12V and ground. The current for
each specified backup period can be
drawn from the batteries with the internal
GSM and the proximity reader connected
to the WP8030.
(2) 7.2V 1300 mAh, rechargeable NiMH
battery pack, p/n 130AAM6BMX,
manufactured by GP or p/n LTT-
AA1300LSDX6B, manufactured by LTT.
(3) 9.6V 1800 mAh, rechargeable NiMH
battery pack, p/n GP180AAH8BMX,
manufactured by GP or p/n LTT-
AA1800LSDX8B, manufactured by LTT.
(4) 9.6V 2200 mAh, rechargeable NiMH
battery pack p/n 220AAH8BMX,
manufactured by GP or p/n LTT-
AA2200LSDX8B, manufactured by LTT.
Caution! Risk of explosion if battery is
replaced by an incorrect type. Dispose of
used batteries according to the
manufacturer's instructions.
Notes:
1. For compliance with CE standards the battery
backup period must be at least 12 hours.
2. For compliance with UL standards the battery
backup period must be at least 24 hours.
Note: Only the LTT-AA2200LSDX8B battery
pack is approved for use by UL.
Time to Charge
80 % ( 13 Hrs)
80 % ( 30 Hrs) for all battery types
Optional Backup
Battery Pack
See "Backup Battery Options" above
See "Backup Battery Options" table above
Time to Charge
(optional backup
battery pack)
80 % ( 24 Hrs)
NA
Wired Detectors
Total (Sum)
Current
NA
36* mA max.
Site External Siren
Current (EXT)
NA
450* mA max @ 12.5 VDC when powered by
AC/DC (10.5 VDC when in standby mode)
Site Internal Siren
Current (INT)
NA
450* mA max @ 12.5 VDC when powered by
AC/DC (10.5 VDC when in standby mode)
* Total WP8030 output current (of INT & EXT
sirens, PGM output and detectors) cannot
exceed 550 mA.
PGM
Current sink to control panel GND 100 mA
max.
Max. external DC voltage +30 VDC
Current sink to control panel GND 100 mA
max.
Max. external DC voltage +15 VDC
High Current /
Short Circuit
Protection
NA
All outputs are protected (automatic reset fuse)

Table of Contents

Other manuals for DSC WP8030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC WP8030 and is the answer not in the manual?

DSC WP8030 Specifications

General IconGeneral
BrandDSC
ModelWP8030
CategoryControl Panel
LanguageEnglish

Related product manuals