6. Function blocks
6.1 Manufacturer function blocks
The counter range has the value zero.
The contacts CI..ZE (actual value equal to zero) and CI..FB (lower threshold value undershot) are act-
ive.
The counter relay receives pulses at I01 and I02 or at I03 and I04 and increments the actual value.
CI..ZE drops out as well as CI..FB after the lower threshold value is reached.
Range B:
The counter relay counts upwards and reaches the upper threshold value.
The “upper setpoint value reached” contact CI..OF becomes active.
Range C:
The coil CI..SE is briefly actuated and the actual value is set to the start value.
The contacts go to the respective position.
Range D:
The counter relay receives pulses at I02 or I04 and decrements the actual value. The function block
counts down.
If the lower threshold value is undershot, the contact CI..FB becomes active.
Range E:
The reset coil CI..RE is activated. The actual value will be set to zero.
The contact CI..ZE is active.
Range F:
The actual value goes outside the value range of the counter relay.
The contacts OF, FB, ZE become active according to the direction of the values (positive or negative).
Retention
Counter relays can be operated with retentive actual values. You can select the number
of retentive counter relays in Project view/System settings tab, please refer to System
settings tab. The retentive ACTUAL value will require 4 bytes of memory space. If a
counter relay is retentive, the actual value will be retained when the operating mode
switches from RUN to STOP and when the power supply is switched off. If the device is
started in RUN mode, the counter relay will continue to work with the non-volatile
actual value.
See also
Section "CI - Incremental counter", page 237
Section "CF - Frequency counter", page 224
Section "CH - High-speed counter", page 230
Section "Timing and counter relay example", page 454
easyE4 11/18 MN050009 EN www.eaton.com
243

Table of Contents

Other manuals for Eaton EASY-E4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EASY-E4 Series and is the answer not in the manual?

Eaton EASY-E4 Series Specifications

General IconGeneral
TypeProgrammable Relay
Digital InputsUp to 12
Digital OutputsUp to 8
DisplayLCD
Operating Temperature-25°C to +55°C
Protection DegreeIP20
Storage Temperature-40°C to +70°C
Supply Voltage24 V DC, 100-240 V AC
Analog Inputs4
OutputsRelay, transistor
ProgrammingEASY-SOFT-PRO
CommunicationEthernet, Modbus, CANopen
ExpansionExpandable with additional modules
Relative Humidity5% to 95% (non-condensing)
StandardsIEC/EN 61131-2, UL 508, CSA C22.2 No. 142

Related product manuals