9. easyE4 inside
9.4 Time behavior of the inputs and outputs
9.4.1 Delay time on EASY-E4-DC-... devices
9.4.1.1 Delay time with DEBOUNCE activated
When DEBOUNCE is activated, the delay time for DC signals is 20 ms.
Figure 239: Delay times for evaluating an DC input signal and an activated DEBOUNCE
An input signal S1 must therefore be > 15V on the input terminal for at least 20 ms
before the switch contact will change from 0 to 1 (A). If applicable, this time must also
include the cycle time (B) since a easyE4 device does not detect the signal until the
start of a cycle.
When the DC voltage signal drops out from 1 to 0 and DEBOUNCE is active, the same
delay time (C) of 20ms is applied before the signal is transferred to the next circuit dia-
gram cycle. For this the input signal S1 must be < 5 V at the input terminal.
easyE4 11/18 MN050009 EN www.eaton.com
507

Table of Contents

Other manuals for Eaton EASY-E4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EASY-E4 Series and is the answer not in the manual?

Eaton EASY-E4 Series Specifications

General IconGeneral
TypeProgrammable Relay
Digital InputsUp to 12
Digital OutputsUp to 8
DisplayLCD
Operating Temperature-25°C to +55°C
Protection DegreeIP20
Storage Temperature-40°C to +70°C
Supply Voltage24 V DC, 100-240 V AC
Analog Inputs4
OutputsRelay, transistor
ProgrammingEASY-SOFT-PRO
CommunicationEthernet, Modbus, CANopen
ExpansionExpandable with additional modules
Relative Humidity5% to 95% (non-condensing)
StandardsIEC/EN 61131-2, UL 508, CSA C22.2 No. 142

Related product manuals