2. Installation
2.4 Connection terminals
2.4.6.1 Transistor output behavior in the event of a short circuit/overload
The following applies to easyE4 devices with transistor outputs:
In the event of a short circuit or overload at a transistor output, this output will switch
off and a general fault alarm ID (please refer to fault IDs) will be set to 1. The output will
switch back on up to the maximum temperature after a cooling time that depends on
the ambient temperature and the current level. If the fault continues, the output will
switch off and on until the fault is rectified or the power supply is switched off.
2.4.6.2 Connecting outputs in parallel
Only outputs of the same group (Q1 to Q4 or Q5 to Q8) can be connected in parallel; e.g.
Q1 and Q3 or Q5, Q7 and Q8. Parallel switched outputs must be similtaneously ener-
gized.
DANGER
If the outputs are not switched on and off automatically, or if outputs
from both groups are connected in parallel, this may result in mal-
functions such as short circuits or the load not switching on
easyE4 11/18 MN050009 EN www.eaton.com
57

Table of Contents

Other manuals for Eaton EASY-E4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EASY-E4 Series and is the answer not in the manual?

Eaton EASY-E4 Series Specifications

General IconGeneral
TypeProgrammable Relay
Digital InputsUp to 12
Digital OutputsUp to 8
DisplayLCD
Operating Temperature-25°C to +55°C
Protection DegreeIP20
Storage Temperature-40°C to +70°C
Supply Voltage24 V DC, 100-240 V AC
Analog Inputs4
OutputsRelay, transistor
ProgrammingEASY-SOFT-PRO
CommunicationEthernet, Modbus, CANopen
ExpansionExpandable with additional modules
Relative Humidity5% to 95% (non-condensing)
StandardsIEC/EN 61131-2, UL 508, CSA C22.2 No. 142

Related product manuals