6. Function blocks
6.3 UF - User function block
Operand
Maximum number
I
12
IA
8
Q
12
QA
8
M
480
MB
64
MW
32
MD
16
These numbers specify the maximum possible number for I, IA, Q, and QA. However,
the following restrictions apply:
l The total number of inputs (bit and analog) must not exceed 12
l The total number of outputs (bit and analog) must not exceed 12
l A maximum of 12 bit inputs and outputs can be used
l A maximum of 8 analog inputs and outputs can be used
Device-specific operands (ID, LE, P) and NET operands (N, NB, NW, ND, RN, SN) are
not supported for user function blocks.
446
easyE4 11/18 MN050009 EN www.eaton.com

Table of Contents

Other manuals for Eaton EASY-E4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EASY-E4 Series and is the answer not in the manual?

Eaton EASY-E4 Series Specifications

General IconGeneral
TypeProgrammable Relay
Digital InputsUp to 12
Digital OutputsUp to 8
DisplayLCD
Operating Temperature-25°C to +55°C
Protection DegreeIP20
Storage Temperature-40°C to +70°C
Supply Voltage24 V DC, 100-240 V AC
Analog Inputs4
OutputsRelay, transistor
ProgrammingEASY-SOFT-PRO
CommunicationEthernet, Modbus, CANopen
ExpansionExpandable with additional modules
Relative Humidity5% to 95% (non-condensing)
StandardsIEC/EN 61131-2, UL 508, CSA C22.2 No. 142