EasyManuals Logo

Eaton EASY-E4 Series User Manual

Eaton EASY-E4 Series
621 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #558 background imageLoading...
Page #558 background image
11. Connection to other devices
11.4 Modbus TCP
Fault Code 1 byte 0x83 ; Read Holding Registers
Exception Code 1 byte 02 or 03 or 04
Exception Code 02 = Starting address is invalid, i.e.:
l 0 (the user keeps specifying addresses as one-based addresses)
l Undefined* (please refer to the "Modbus map" table) or
l Un-enabled*
Exception Code 03 = The number of inputs is not >= 0x0001 and <= 0x07D0
Exception Code 04 = (Error in server) n.a.**
If no analog I/O is physically present (e.g., analog I/O smart modules missing or faulty),
the image table (values = 0) will still be delivered to the client. No check, no error mes-
sage.
*For an error message, it is sufficient if only one of the requested addresses is not
unlocked or is invalid.
**A read operation always returns consistent data from the image table, since this data
is protected from other modules by semaphores. In other words, as of this writing,
there is no known criterion for a "read holding registers" error in the server.
Read Input Registers 0x04:
In the event of an error, Modbus TCP will send an error frame.
Fault Code 1 byte 0x84 ; Read Input Registers
Exception Code 1 byte 02 or 03 or 04
Exception Code 02 = Starting address is invalid, i.e.:
l 0 (the user keeps specifying addresses as one-based addresses)
l Undefined* (please refer to the "Modbus map" table) or
l Un-enabled*
Exception Code 03 = The number of inputs is not >= 0x0001 and <= 0x07D0
Exception Code 04 = (Error in server) n.a.**
If no analog I/O is physically present (e.g., analog I/O smart modules missing or faulty),
the image table (values = 0) will still be delivered to the client. No check, no error mes-
sage.
*For an error message, it is sufficient if only one of the requested addresses is not
unlocked or is invalid.
**A read operation always returns consistent data from the image table, since this data
is protected from other modules by semaphores. In other words, as of this writing,
there is no known criterion for a "read input registers" error in the server.
554
easyE4 11/18 MN050009 EN www.eaton.com

Table of Contents

Other manuals for Eaton EASY-E4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EASY-E4 Series and is the answer not in the manual?

Eaton EASY-E4 Series Specifications

General IconGeneral
TypeProgrammable Relay
Digital InputsUp to 12
Digital OutputsUp to 8
DisplayLCD
Operating Temperature-25°C to +55°C
Protection DegreeIP20
Storage Temperature-40°C to +70°C
Supply Voltage24 V DC, 100-240 V AC
Analog Inputs4
OutputsRelay, transistor
ProgrammingEASY-SOFT-PRO
CommunicationEthernet, Modbus, CANopen
ExpansionExpandable with additional modules
Relative Humidity5% to 95% (non-condensing)
StandardsIEC/EN 61131-2, UL 508, CSA C22.2 No. 142

Related product manuals