Contextual help of the web interface – 134
•
•
•
•
The log in screen appears.
Enter the user name in the User Name field.
Enter the password in the Password field.
ClickLogin. The Network Module web interface appears.
STEP 2:Navigate toProtection/Agents listpage.
STEP 3:In thePairing with shutdown agentssection, select the time to accept new agents and press theStartbutton
andContinue. During the selected timeframe, new agent connections to the Network Module are automatically trusted and
accepted.
STEP 4:Action on the agent( IPP/IPM )while the time to accepts new agents is running on the Network Module
Remove theNetwork module certificate file(s) *.0that is (are) located in the folder
Eaton\IntelligentPowerProtector\configs\tls.
Card wrong timestamp leads to "Full acquisition has failed" error message on Software
Symptoms:
IPP/IPM shows the error message"The full data acquisition has failed" even if the credentials are correct.
Possible cause:
The Network module timestamp is not correct.
Probably the MQTT certificate is not valid at Network module date.
Action:
Set the right date, time and timezone. If possible, use a NTP server, refer to Contextual
help>>>Settings>>>General>>>System details>>>Time & date settings section.
3.7.7.8.1 For other issues
For details on other issues, see the Troubleshooting section.