EasyManua.ls Logo

Eaton Network-M2 - Meters; Sensors Alarm Configuration

Eaton Network-M2
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Default settings and possible parameters
Information – 219
7.3.2 Meters
Default settings and possible parameters - Meters
Default setting Possible parameters
Meters/Logs Log measures every—60s Log measures every — 3600s maximum
7.3.3 Sensors alarm configuration
Default settings and possible parameters - Environment Alarm configuration
Default setting Possible parameters
Temperature Enabled—No
Low critical – 0°C/32°F
Low warning – 10°C/50°F
High warning – 70°C/158°F
High critical – 80°C/176°F
Enabled—No/Yes
low critical<low warning<high warning<high critical
Humidity Enabled—No
Low critical – 10%
Low warning – 20%
High warning – 80%
High critical – 90%
Enabled—No/Yes
0%<low critical<low warning<high warning<high
critical<100%
Dry contacts Enabled—No
Alarm severity – Warning
Enabled—No/Yes
Alarm severity – Info/Warning/Critical

Table of Contents