List of event codes
Information – 229
811 Critical Parallel negative power Parallel power OK Reduce output load
815 Critical Calibration fault Calibration OK Service required
81E Critical Load unprotected Load protected -
7.5.2.2 Warning
Code Severity Active message Non-active message Advice
001 Warning On battery No more on battery -
007 Warning Fan fault Fan OK Service required
00B Warning Parallel UPS redundancy lost Parallel UPS redundancy OK Reduce output load
00E Warning Parallel UPS communication lost Parallel UPS communication OK Service required
00F Warning Parallel UPS not compatible Parallel UPS compatibility OK Service required
010 Warning UPS power supply fault UPS power supply OK Service required
011 Warning Parallel UPS protection lost Parallel UPS protection OK Reduce output load
012 Warning Parallel UPS measure inconsistent Parallel UPS measure OK Service required
103 Warning Utility breaker open Utility breaker closed -
104 Warning Input AC frequency out of range Input AC frequency in range -
106 Warning Input AC not present Input AC present -
107 Warning Input bad wiring Input wiring OK Check input wiring
108 Warning Input AC voltage out of range (-) Input AC voltage in range -
109 Warning Input AC voltage out of range (+) Input AC voltage in range -
110 Warning Building alarm (through dry
contact)
Building alarm OK -
11F Warning Building alarm (through Network
module)
Building alarm OK -
10A Warning Input AC unbalanced End of input AC unbalanced -
200 Warning Bypass phase out range Bypass phase in range -
201 Warning Bypass not available Bypass available Service required
202 Warning Bypass thermal overload Bypass thermal OK Reduce output load
203 Warning Bypass temperature alarm Bypass temperature OK Check air conditioner
204 Warning Bypass breaker open Bypass breaker closed -
205 Warning Bypass mode No more on bypass -
206 Warning Bypass frequency out of range Bypass frequency in range -
209 Warning Bypass voltage out of range Bypass voltage in range -
20A Warning Bypass AC over voltage End of bypass AC over voltage -
20B Warning Bypass AC under voltage End of bypass AC under voltage -
20C Warning Bypass bad wiring Bypass wiring OK Check bypass wiring
300 Warning DC bus + too high DC bus + voltage OK Service required
301 Warning DC bus - too high DC bus - voltage OK Service required
302 Warning DC bus + too low DC bus + voltage OK Service required
303 Warning DC bus - too low DC bus - voltage OK Service required
304 Warning DC bus unbalanced DC bus OK Service required
501 Warning Charger temperature alarm Charger temperature OK Service required