816 Warning Compatibility failure Compatibility OK Service required
817 Warning Output over current No output over current Reduce output load
818 Warning Output frequency out of range Output frequency in range Service required
819 Warning Output voltage too high Output voltage OK Service required
81A Warning Output voltage too low Output voltage OK Service required
81B Warning UPS Shutoff requested End of UPS shutoff requested Service required
81D Warning Load not powered Load protected -
900 Warning Maintenance bypass Not on maintenance bypass -
901 Warning Maintenance bypass breaker
closed
Maintenance bypass breaker open -
B01 Warning Batteries are aging. Consider
replacement
Batteries aging condition cleared -
7.5.2.3 Info
Code Severity Active message Non-active message Advice
005 Info Communication lost (with UPS) Communication recovered (with
UPS)
Service required
009 Info On high efficiency / On ESS mode High efficiency disabled / ESS
disabled
-
013 Info Upgrading: limited communication End of upgrade mode -
101 Info On AVR (Boost) End of AVR (Boost) -
102 Info On AVR (Buck) End of AVR (Buck) -
603 Info Battery discharging End of UPS battery discharge -
63C Info Battery information Battery OK -
A00 Info Group 1 is OFF Group 1 is ON -
A01 Info Group 2 is OFF Group 2 is ON -
A0F Info Group is OFF Group is ON -
7.5.2.4 Good
Code Severity Active message
60E Good UPS external battery set as “No battery”
826 Good Load powered
Alarms with a severity set as Good are not taken into account into the counter of active alarms.