EasyManua.ls Logo

Eaton PowerXL DC1 Series - Page 214

Eaton PowerXL DC1 Series
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Annex
11.12 Mains contactors
208 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Table 26: Assigned mains contactors
Device type
Rated operating voltage Rated input
current
Related mains contactor
DC1…
(50 Hz) (60 Hz) Part no. Thermal current AC-1
+50 °C +40 °C
U
LN
U
LN
I
LN
I
N
I
N
[A] [A] [A]
DC1-1D2D3 1AC110V 1AC120V 11 DILEM-10 + DILM12-XP1 20 22
DC1-1D4D3 1AC110V 1AC120V 19 DILEM-10 + DILM12-XP1 20 22
DC1-1D5D8
1AC110V 1AC120V 25 DILEM-10 + DILM12-XP1 20 22
DC1-122D3…
1AC230V 1AC240V 5 DILEM-10 + DILM12-XP1
DILM7
2)
20
21
22
DC1-124D3…
1AC230V 1AC240V 8.5 DILM7 21 22
DC1-127D0FN 1AC230V 1AC240V 13.9 DILM7 21 22
DC1-127D0FB… 1AC230V 1AC240V 13.9 DILM7 21 22
DC1-12011…
1AC230V 1AC240V 19.5 DILM17 38 40
DC1-12015… 1AC230V 1AC240V 30.5 DILM17 38 40
DC1-322D3… 3AC 230V 3AC240V 3.0 DILEM-10 20 22
DC1-324D3… 3AC 230V 3AC240V 4.5 DILEM-10 20 22
DC1-327D0FN 3AC 230V 3AC240V 7.3 DILEM-10 20 22
DC1-327D0FB… 3AC 230V 3AC240V 7.3 DILEM-10 20 22
DC1-32011… 3AC 230V 3AC240V 11.0 DILM7 21 22
DC1-32018… 3AC 230V 3AC240V 18.8 DILM7
DILM17
1)
21
38
22
40
DC1-342D2…
3AC400V 3AC480V 2.4 DILEM-10 20 22
DC1-344D1FN
3AC400V 3AC480V 4.3 DILEM-10 20 22
DC1-344D1FB…
3AC400V 3AC480V 4.3 DILEM-10 20 22
DC1-345D8… 3AC400V 3AC480V 6.1 DILEM-10 20 22
DC1-349D5… 3AC400V 3AC480V 9.8 DILEM-10 20 22
DC1-34014… 3AC400V 3AC480V 14.6 DILM7 21 22
DC1-34018…
3AC400V 3AC480V 18.1 DILM7 21 22
DC1-34024…
3AC400V 3AC480V 24.7 DILM17 38 40
1) For UL® installation observe note Page 208
2) Maximum operating temperature +40 °C
For UL®-compliant installation and operation, the switchgear on
the mains side must allow for an input current that is 1.25 times
higher. The switchgear listed here meets this requirement.

Table of Contents