11 Annex
11.12 Mains contactors
208 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Table 26: Assigned mains contactors
Device type
Rated operating voltage Rated input
current
Related mains contactor
DC1…
(50 Hz) (60 Hz) Part no. Thermal current AC-1
+50 °C +40 °C
U
LN
U
LN
I
LN
I
N
I
N
[A] [A] [A]
DC1-1D2D3… 1AC110V 1AC120V 11 DILEM-10 + DILM12-XP1 20 22
DC1-1D4D3… 1AC110V 1AC120V 19 DILEM-10 + DILM12-XP1 20 22
DC1-1D5D8…
1AC110V 1AC120V 25 DILEM-10 + DILM12-XP1 20 22
DC1-122D3…
1AC230V 1AC240V 5 DILEM-10 + DILM12-XP1
DILM7
2)
20
21
22
DC1-124D3…
1AC230V 1AC240V 8.5 DILM7 21 22
DC1-127D0FN… 1AC230V 1AC240V 13.9 DILM7 21 22
DC1-127D0FB… 1AC230V 1AC240V 13.9 DILM7 21 22
DC1-12011…
1AC230V 1AC240V 19.5 DILM17 38 40
DC1-12015… 1AC230V 1AC240V 30.5 DILM17 38 40
DC1-322D3… 3AC 230V 3AC240V 3.0 DILEM-10 20 22
DC1-324D3… 3AC 230V 3AC240V 4.5 DILEM-10 20 22
DC1-327D0FN… 3AC 230V 3AC240V 7.3 DILEM-10 20 22
DC1-327D0FB… 3AC 230V 3AC240V 7.3 DILEM-10 20 22
DC1-32011… 3AC 230V 3AC240V 11.0 DILM7 21 22
DC1-32018… 3AC 230V 3AC240V 18.8 DILM7
DILM17
1)
21
38
22
40
DC1-342D2…
3AC400V 3AC480V 2.4 DILEM-10 20 22
DC1-344D1FN…
3AC400V 3AC480V 4.3 DILEM-10 20 22
DC1-344D1FB…
3AC400V 3AC480V 4.3 DILEM-10 20 22
DC1-345D8… 3AC400V 3AC480V 6.1 DILEM-10 20 22
DC1-349D5… 3AC400V 3AC480V 9.8 DILEM-10 20 22
DC1-34014… 3AC400V 3AC480V 14.6 DILM7 21 22
DC1-34018…
3AC400V 3AC480V 18.1 DILM7 21 22
DC1-34024…
3AC400V 3AC480V 24.7 DILM17 38 40
1) For UL® installation observe note → Page 208
2) Maximum operating temperature +40 °C
→
For UL®-compliant installation and operation, the switchgear on
the mains side must allow for an input current that is 1.25 times
higher. The switchgear listed here meets this requirement.