4.5.4 AC Wiring Information
When sizing AC wires please adhere to the following information.
Cable Requirements:
Terminal Connection Wire Size Torque Values
GRID 6-4/0 AWG (26.7-107mm²)
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
GEN
Size according to generator
output
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
LOAD
6-4/0 AWG (26.7-107mm²)
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
See wiring diagrams in Section 5 for more information.
Ground-Neutral Bonding
The information below describes the nature of the ground and neutral in the inverter and their relation-
ship to the system. Always consult with your installer or a licensed electrician to ensure that the right
configuration is being used:
• The neutral line is a solid connection between AC input and AC output (known as a Common
Neutral Architecture).
• The neutral line between the AC input and AC output is never disconnected.
• The inverter never creates a ground-neutral bond in any mode of operation.
• The AC grounds, the PV grounds, and the inverter case are all permanently tied together.
Important
The system should have one and only one ground-neutral bond. (This is typically the Main Bonding
Jumper located at the first grid system disconnect.)