20
4.5.4 AC Wiring Information
When sizing AC wires please adhere to the following information.
Cable Requirements:
Terminal Connection Wire Size Torque Values
GRID 6-4/0 AWG (26.7-107mm²)
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
GEN
Size according to generator
output
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
LOAD
6-4/0 AWG (26.7-107mm²)
95-165 in. lbs. (10.7Nm-
18.6Nm) depending on wire
See wiring diagrams in Section 5 for more information.
Ground-Neutral Bonding
The information below describes the nature of the ground and neutral in the inverter and their relation-
ship to the system. Always consult with your installer or a licensed electrician to ensure that the right
configuration is being used:
The neutral line is a solid connection between AC input and AC output (known as a Common
Neutral Architecture).
The neutral line between the AC input and AC output is never disconnected.
The inverter never creates a ground-neutral bond in any mode of operation.
The AC grounds, the PV grounds, and the inverter case are all permanently tied together.
Important
The system should have one and only one ground-neutral bond. (This is typically the Main Bonding
Jumper located at the first grid system disconnect.)

Table of Contents

Other manuals for EG4 18KPV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EG4 18KPV and is the answer not in the manual?

EG4 18KPV Specifications

General IconGeneral
ModelEG4 18KPV
CategoryInverter
Rated Power18 kW
Max. AC Output Current75A
Surge Power36 kW
Number of MPPTs2
Frequency50/60 Hz
Operating Temperature-25°C to 60°C
Warranty5 years
Output Voltage120/240VAC
CommunicationRS485
CoolingFan
Weight77 lbs (35 kg)
Dimensions670 x 530 x 220 mm