Installing a cluster
23
Installing the Hardware
5. From the front of the cabinet, remove each engine’s bezel as shown in Figure 7 ,
and verify that the two power supply modules, four fan modules, and solid state
drive (SSD) enclosure are fully inserted and secure.
Figure 7 Engine components: Front view
Task 3: Stabilize the
equipment
The equipment requires time to become acclimated to a data center environment.
Table 2 lists the required times.
a. Temperature and humidity values must be such that condensation does not occur on any VPLEX component.
CL4341c
!
!
Power supply
Fan
SSD enclosure
Table 2 Data center acclimation times
Transit/storage environment Hours required
before applying
powerCondition Temperature range Relative humidity
Nominal 68
o
to 72
o
F(20
o
to 22
o
C) Less than 30% 0
Cool / Damp Less than 68
o
F(20
o
C) 30% or greater 4
Cold / Dry Less than 20%
Hot / Dry 72
o
to 90
o
F(22
o
to 32
o
C) Less than 30%
Hot / Humid
a
30% to 45%
45% to 60% 8
60% to 80% 16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EMC VPLEX and is the answer not in the manual?

EMC VPLEX Specifications

General IconGeneral
Data MobilityYes
ReplicationSynchronous and asynchronous
VirtualizationYes
CategoryStorage
VendorEMC
FunctionStorage virtualization, data mobility, replication, high availability, disaster recovery
High AvailabilityYes
Disaster RecoveryYes
ConnectivityFibre Channel, iSCSI

Related product manuals