DL8000 Preset Instruction Manual
Revised February-2016 DL8000 Keypad Display E-5
A primary (or critical) alarm is active. You must
clear this alarm before you can begin a new
batch or new transaction.
A secondary (non-critical) alarm is active.
E.1.3 Liquid Crystal Display (LCD)
The DL8000 screen provides a Class 1, Div 1 liquid crystal display,
which displays text, numbers, and graphics. The LCD has two halves:
the left half displays 8 rows of 19 characters and the right half displays
8 rows of 20 characters (see Figure E-3). A single navigation program
controls the screen.
Select from the
Following Recipes
(ENTER to Continue)
Recipe #1
Recipe #2
Recipe #3
Recipe #4
Recipe #5
A. Weights & Measures Icon (in closed or locked position)
Figure E-3. LCD Screen (Loading Mode)
The Weights & Measures icon (shown locked in Figure E-3) always
appears in the upper left corner of the left-hand screen and indicates the
current status of the Weights & Measures switch.
E.1.4 Power Failure
If power fails to the keypad display (but not to the DL8000 itself) for
more than 5 seconds or if communications fail to the keypad display for
more than 5 seconds, the system generates the Keypad Display
Communications Failure (K & D Com. Fail) alarm (if you have
previously configured it [TLP 64,0,42]).
In the event of power failure, the program redisplays the screen when
power is restored. If the preset was in program mode when the power
failure occurred, the keypad display program exits program mode and
redisplays the most previous loading mode screen.
In the event of communications failure, the program redisplays the
screen when communications are restored. If the preset was in program
mode, the keypad display program exits program mode and redisplays
the most previous loading mode screen.