DL8000 Preset Instruction Manual
3-6 Modules Revised February-2016
You can insert or remove the I/O modules while power is connected to
the DL8000. If the DL8000 is powered, exercise caution while
performing the following steps to install a module.
Note: After you install a new I/O module or replace an existing I/O
module, it may be necessary to reconfigure the DL8000. To
change configuration parameters, use ROCLINK 800 software
to make changes to the new module. Any added modules (new
I/O points) start up with default configurations. Refer to the
ROCLINK 800 Configuration Software User Manual (for
DL8000) (part D301259X012).
3.2.2 Installing an I/O Module
To install an I/O module:
1. Remove the wire channel cover.
Note: Leaving the wire channel cover in place can prevent the
module from correctly connecting to the socket on the
backplane.
2. Perform one of the following:
If there was previously a module in the slot, unscrew the captive
screws and remove that module.
If the slot was previously unused, remove the module cover.
3. Insert the new I/O module into the module slot in the card cage.
Make sure the label on the front of the module is facing right side
up. Gently slide the module in place until it contacts the connectors
on the backplane.
Note: If the module stops and will not go any further, do not force
the module. Remove the module and see if the pins are bent.
If so, gently straighten the pin(s) and re-insert the module.
The back of the module must connect fully with the
connectors on the backplane.
4. Tighten the captive screws on the front of the module.
5. Wire the I/O module (refer to Section 3.2.4, Wiring I/O Modules).
6. Replace the wire channel cover.
Caution
Never connect the sheath surrounding shielded wiring to a signal
ground terminal or to the common terminal of an I/O module. Doing so
makes the I/O module susceptible to static discharge, which can
permanently damage the module. Connect the shielded wiring only to a
suitable earth ground.
7. Connect to ROCLINK 800 software and login. The I/O modules are
self-identifying after re-connecting to ROCLINK 800 software.