EasyManua.ls Logo

Emerson DL8000 - EIA-422;485 (RS-422;485) Jumpers and Termination Resistors; Resistors; RS-422) Module

Emerson DL8000
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL8000 Preset Instruction Manual
3-40 Modules Revised February-2016
The default values for the EIA-422/485 (RS-422/485) communications
are: 19200 Baud rate, 8 data bits, 1 stop bit, and no parity. The
maximum rate is 57.6K bps.
EIA-422/485 (RS-422/485) communication modules include LED
indicators that display the status of receive and transmit activity. See
Tables 3-14 and 3-15.
Table 3-14. EIA-422 (RS-422) Signal Routing – Comm3, Comm4, and Comm5
Signal
RS-422
Function
Terminal
A
RX +
Lit when module (Comm3, Comm4, or Comm5) is currently receiving.
1
B
RX
None.
2
Y
TX +
Lit when module (Comm3, Comm4, or Comm5) is currently transmitting.
3
Z
TX
None.
4
COM
Common
Ground.
5
Table 3-15. EIA-485 (RS-485) Signal Routing – Comm3, Comm4, and Comm5
Signal
RS-485
Function
Terminal
A
RX / TX +
Lit when module (Comm3, Comm4, or Comm5) is currently receiving.
1
B
RX / TX
Lit when module (Comm3, Comm4, or Comm5) is currently transmitting.
2
Y
No Connect
None.
3
Z
No Connect
None.
4
COM
Common
Ground.
5
Note: The EIA-422/485 (RS-422/485) modules are isolated on the field
side.
Caution
You can induce ground loops by tying commons from various modules
together.
EIA-422/485 (RS-422/485) communications provides EIA-422/485
(RS-422/485) signals on the Comm3, Comm4, or Comm5 port
depending on where the module is installed. Wiring should be twisted-
pair cable, one pair for transmitting, and one pair for receiving. The
EIA-422 (RS-422) module uses four wires and the EIA-485 (RS-485)
uses two wires for connectivity.
3.3.7 EIA-422/485 (RS-422/485) Jumpers and Termination Resistors
Four jumpers—J3, J4, J5, and J6—are located on the EIA-422/485 (RS-
422/485) communications module (see Figure 3-41). These jumpers
determine in which mode the module runs (RS-422 or RS-485) and if
the module is terminated. See Tables 3-16 and 3-17.
Terminations are required on the two EIA-422/485 (RS-422/485)
communication modules located at the extremities of the circuit. That is
to say, the two outside modules require terminations in order to
complete the communications circuit.

Table of Contents

Other manuals for Emerson DL8000

Related product manuals