D-44 Communications Protocols Revised February-2016
Batch Data
by Component
[0x10]
Deviations
For Version 1.0: DL8000 does not support swing
side arm, so it always returns a value of 1 in the
command response frame.
For
Version 2.0
: None
Additive Totalizer
[0x11]
Displays the free running totals of all additives according to the configured
number of additives.
Flags Immediately Set
None
Flags Immediately
Cleared
None
Exceptions
Additives Module is not running in preset.
Supporting
Parameters
As below.
Results
The response frame includes the following
parameter values:
Number of additives [63,0,100]
Additive free running totals [67,x,12]
Deviations
None
Request Status
[0x12]
Displays the overall status of the DL8000. For the command response, see the
Results section.
Status flags is a binary representation of the DL8000’s 32 status flags.
Safety circuit status is the current logical state (“open” or “closed”) of 8 general
purpose safety circuit inputs. The least significant bit is safety circuit 1 etc. If
you do not configure the safety circuit input then value of bit for respective
safety circuit will be equal to unsafe state [0].
Alarm bitmaps indicate active (raised and not reset) alarms. The automation
system can maintain a copy of the “alarm bytes” so that it can determine (for
logging purposes) when alarms are raised or cleared.
Flags Immediately Set
None
Flags Immediately
Cleared
None
Exceptions
None
Supporting Parameters
As below