EasyManua.ls Logo

Emerson DL8000 - Modbus Configuration Scale Values Tab

Emerson DL8000
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL8000 Preset Instruction Manual
Revised February-2016 Modbus Communications B-5
2. Click Apply to save any changes you have made to this screen.
3. Proceed to Section B.2.2 to define scale values.
B.2.2 Modbus Configuration Scale Values Tab
Select the Scale Values tab to enter up to eight low and high floating
point scale values and one low and high integer values for converting
floating point numbers to a scaled integer.
Figure B-2. Modbus Configuration – Scale Values Tab
Scale
Since each I/O point may have different scaling (or calibration), you
use the Integer Scale’s Low Value and High Value fields to normalize
the raw values from the analog I/O points.
The Low Value and High Values fields are signed integers, and can
range from –32768 to 32767. You can also use these data fields to scale
the analog I/O to integer values with an implied decimal point.
For example, all analog I/O raw values can be transmitted with 0 to
1000 values (0 to 100.0, decimal point implied) by entering 0 in the
Low Value field and 1000 in the High Value field. This scaling is used

Table of Contents

Other manuals for Emerson DL8000

Related product manuals