DL8000 Preset Instruction Manual
Revised February-2016 DL8000 Keypad Display E-57
After you provide all the parameters required for calibration press
ENTER to continue. The program then displays the live value from an
external source with a corresponding “dead” (expected) value you can
change.
Enter ZERO EU
Enter SPAN EU
(ENTER to update )
80.3000003 80.5
Press ENTER to update the value. You then enter a span value:
Enter ZERO EU
Enter SPAN EU
(ENTER to update )
80.3000003 80.5
229.000000 228.99
If you need mid-points for calibration, enter those next.
The program checks all values you enter. If any value is not within
accepted ranges, the program displays the error message
InvdEntry!ReEnter:
Enter ZERO EU
Enter SPAN EU
(ENTER to update )
80.3000003 80.5
229.000000 228.99
InvdEntry!ReEnter
You must re-enter those values in order to proceed.
Valid ranges are:
RTD unit Minimum Range Maximum Range
Deg F -58.0 662.0
Deg C -50.0 350.0
Deg K 223.15 623.15
Deg R 401.67 1121.67
OHM 80.31 229.72