DL8000 Preset Instruction Manual
E-50 DL8000 Keypad Display Revised February-2016
14/03/12 12:26:02
WM Switch is Closed
Pls open the Switch
And try again
You must open the W&M switch in order to perform calibrations.
E.4.1 Calibrating Additive Meters
Select Additive Calib to start the additive calibration process.
14/03/12 12:26:02
For traversing use
UP | DOWN
LEFT | RIGHT
ENTER to continue
EXIT to Go Back
EXIT to quit
Additive Calib
Analog Calib
RTD Calib
PRODUCT Calib
(Pg:1/1)
If no additives are currently configured, the preset displays the
following screen:
14/03/12 12:26:02
Adtv not configured
EXIT to quit
Press EXIT to quit; no calibration is possible.
In addition to the number of configured additives, the program can
display the following error messages:
Error Message Description
Adtv Prog. Not Available or
Running
The additive program (#4) is not loaded
or running.
Invalid Injection Method
The value of the injection method
[67,X,1] is not Control (value 3)
K.F not configured
The Volume oper pulse/K factor
parameter [67,x,2] is set to
0
M.F not configured
The Additive Meter Factor parameter
[67,x,28] is set to 0