DL8000 Preset Instruction Manual
Revised February-2016 Modules 3-21
Terminal
Label
Definition
9 6 Channel 6
10 N AC Neutral
The field terminal wiring has the following definitions:
Term
Definition
AC Input
The AC power applied to this terminal is the source for
any channel that is configured as an output. The input to
this terminal should be externally fused with a 10 to 15
amp fuse. The channel has a green LED associated with it
to indicate when power is applied. This terminal is typically
wired to the permissive/safety circuitry so that if this circuit
trips, all power is removed from the channels that are
configured as AC outputs.
AC Neutral
This terminal is connected to the system AC neutral and is
used a reference for all AC power.
Channels 1
through 6
Depending upon the configuration of the DIP switch, each
channel can be configured as an input or an output.
Multiple AC I/O
Modules
If you need to install more than one AC I/O module in the DL8000,
wire the modules as shown in Figures 3-19 and 3-20.