DL8000 Preset Instruction Manual
E-92 DL8000 Keypad Display Revised February-2016
If you define an internal AC I/O module for both AC input and AC
output, after you select the required channels press ENTER to start the
diagnostics:
14/03/12 12:26:02
Use AC Output Ch
Use AC Input Ch
AC O/p curr Sts
AC I/p curr Sts
(SEL to toggle Sts)
Ac ch 7
AC ch 1
ON
ON
(STOP to End )
Press SELECT to toggle the status of AC output channel. The status of
the AC load/AC input should change accordingly.
Press STOP to end the test for the current channel and to then select a
new channel for test.
The AC I/O module detects the input and output channels of connected
modules and shows these values during channel selection. For example,
if you set three channels on an AC I/O module to input and three
channels to output, the program displays channels 1-3 as inputs and
channels 4-6 as outputs.
Affected
TLPs
When you select this test, the system sets certain ACIO module
parameters to specific values to perform the test (as noted below). Once
you complete the test, the system restores all TLP to the values they had
before the test began.
Channel Mode [140,X,2]
Scanning Input [140,X,3]
Input Invert Mode [140,X,9]
Latch Mode [140,X,10]
Scanning Output [140,X,18]
Manual Output [140,X,20]
Momentary Mode [140,X,25]
Toggle Mode [140,X,27]
Times Discrete Output (TDO) Mode [140,X,28]
Invert Output Mode [140,X,29]
If you set both channels to NONE, the program performs no diagnostics
and displays the Config Error message: