EasyManua.ls Logo

Emerson DL8000 - Page 46

Emerson DL8000
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL8000 Preset Instruction Manual
3-8 Modules Revised February-2016
If required, you can calibrate the low end of the analog signal to zero
(refer to Chapter 7 in the ROCLINK 800 Configuration Software User
Manual) (for DL8000) (part D301259X012).
Note: The AI-16 module provides 16-bit resolution and uses a 24-bit
A/D converter. DIP switches on the AI-16 control the scaling
(see Figure 3-6).
You can configure the AI (+T) as either 12 or 24 Volts dc using jumper
J4 on the AI-12 module (see Figure 3-4). The AI modules can provide
isolated +12 Volts dc or +24 Volts dc field transmitter power on a per
module basis. For example, one module can provide +12 Volts dc for
powering low-power analog transmitters, while another module in the
same DL8000 controller can provide +24 Volts dc for powering
conventional 4 to 20 mA transmitters. See Figure 3-5.
Figure 3-4. AI-12 Jumper J4 (Shown Set to +12V)
1-5 VOLT DEVICE
EXTERNALLY POWERED
+
-
1-5 VOLT DEVICE
EXTERNALLY POWERED
+
-
ROC809 POWERED
CURRENT LOOP DEVICE 4-20mA
-
+
OUT SIGNAL
COM IN
DOC0506A
Figure 3-5. Analog Input Module Field Wiring
Precision
Resistor
+T 12 / 24 V dc
Jumper