126
Reference Manual
00809-0100-4026, Rev KC
Configuration
October 2018
Configuration
Restart transmitter
15.Restart the transmitter to activate all of the configuration changes. It may take up to 60 seconds after the restart
button is pressed before measurement values are updated.
Verify level
16.Run the Verify Level tool to match the product level reported by the device to a reference measurement
(measured by using for example hand gauging). In any difference, the Calibration Distance parameter will be
adjusted.
A minor adjustment using Calibration Distance is normal. There may, for example be a deviation between the
actual tank height and the configured value.