Level Transducer Block
Table E-15. Volume
E.4 Diagnostics device errors
In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on the
measurement status can be obtained via SENSOR_DIAGNOSTICS. Table H-1 on page 309 lists the
potential errors and the possible corrective actions for the given values. The corrective actions are in
order of increasing system level compromises. The first step should always be to reset the gauge and
then if the error persists, try the steps in Table H-1 on page 309. Start with the first corrective action and
then try the second.
Value Display Description
0
(1)
1. Default only for parameter LCD_VOLUME_UNIT.
Default
Unit for LCD display is the same as set in the value
window
1034 M
3
Cubic meter
1038 L Liter
1042 In
3
Cubic Inch
1043 Ft
3
Cubic feet
1044 Yd
3
Cubic yard
1048 Gallon US gallon
1049 ImpGall Imperial gallon
1051 Bbl Barrel (oil)