13
Reference Manual
00809-0100-4026, Rev KC
Introduction
October 2018
Introduction
Table 2-4. Model and Antenna Guide
Model and antenna guide
Rosemount 5402 Rosemount 5401
This table gives guidelines on which
model and antenna to select, depending
on application.
G = Good
AD = Application Dependent (contact
your local Emerson Automation Solution
representative)
NR = Not Recommended
Cone (preferred) Process seal Parabolic Cone (preferred) Rod
Best choice for a
broad range of
applications, free
propagation and
pipe installations.
Ideal for small tanks
and corrosive
applications. Good for
heavy antenna
condensation/build-up.
Only for solids
applications. Good
for long ranges.
Suitable for some
extreme process
conditions.
Suitable for small
process
connections, and
corrosive
environment.
Tank considerations
Installation close to smooth tank wall G G AD G G
Multiple units on the same tank G G G G G
Internal obstructions, directly in path
(1)
NR NR NR AD AD
Internal obstructions, avoidance
(1)
G G AD NR NR
Beam angle 2” 19°
3” 14°
4” 9°
2” 19°
3” 14°
4” 9°
4.5° 4” 37°
6” 23°
8” 17°
37°
Antenna extends below nozzle G G G G G
Antenna recessed in smooth nozzle up
to 6 ft (2 m)
GG
NR NR
(2)
NR
(3)
Antenna recessed in nozzle with
irregularities, such as bad welds
AD
(4)
AD AD AD
(4)
NR
(3)
Stilling well mounting G (2- to 4-in. pipe) G (2- to 4-in. pipe) NR G (3- to 8-in. pipe) NR
Valves G G NR NR NR
Long ranges (>115’/35 m) NR NR NR NR NR
Cleanability of antenna AD G G
(5)
AD G
Process medium characteristics
Vapor (light, medium) G G G G G
Vapor (heavy) NR AD AD G G
Condensing vapor/product build-up
(6)
AD G G
(5)
GAD
Boiling/Turbulent surface (low/medium) G G G G G
Boiling/Turbulent surface (heavy) AD AD G G
(7)
NR
Boiling/Turbulent surface (still-pipe) G G NR G NR
Foam
(8)
NR NR N/A AD AD
Foam (still-pipe)
(8)
GG NRGNR
Corrosive products (options available) G
(9)
G
(9)
NR G
(9)
G