Safety 
Information
Introduction
Product 
Information
System 
configuration
Mechanical 
Installation
Electrical 
Installation
Getting 
Started
Basic 
parameters
Running 
the motor
Optimization
SMARTCARD 
operation
Onboard 
PLC
Advanced 
parameters
Technical 
Data
Diagnostics
UL Listing 
Information
246  Unidrive SPM User Guide
www.controltechniques.com                               Issue Number: 3
SM-LON parameters
Parameter
Range(
Ú) Default(Ö)
Type
x.01 Solutions Module ID 0 to 599 401 RO Uni PT US
x.02 Solutions Module software version 0.00 to 99.99 RO Uni NC PT
x.03 Node ID 0 to 127 0 RW Uni
x.06 Option module diagnostic information -9999 to 9999 0 RW Uni
x.07 Network loss trip 0 to 1 0 RW Uni
x.10 Subnet ID 0 to 255 0 RW Uni
x.11 Domain ID length 0 to 6 0 RW Uni
x.12 Domain ID byte 1 0 to 255 0 RW Uni
x.13 Domain ID byte 2 0 to 255 0 RW Uni
x.14 Domain ID byte 3 0 to 255 0 RW Uni
x.15 Domain ID byte 4 0 to 255 0 RW Uni
x.16 Domain ID byte 5 0 to 255 0 RW Uni
x.17 Domain ID byte 6 0 to 255 0 RW Uni
x.30 Load Option Defaults Off (0) or On (1) Off (0) RW Bit
x.31 Save option parameters Off (0) or On (1) Off (0) RW Bit
x.32 Request to re-initialise Off (0) or On (1) Off (0) RW Bit
x.33
Restore parameters from option 
module
Off (0) or On (1) Off (0) RW Bit
x.34 Initialise drive reference selectors Off (0) or On (1) Off (0) RW Bit
x.35 Option module serial number
-2147483648 to 2147483647
RO Bi NC PT
x.36 Transmit service pin message Off (0) or On (1) Off (0) RW Bit
x.37 Wink active Off (0) or On (1) Off (0) RW Bit
x.38 Unconfigure option module 0 to 1 0 RW Uni
x.39 Default configuration property storage 0 to 1 0 RW Uni
x.50 Module error status 0 to 255 RO Uni NC PT
x.51 Module software sub-version 0 to 99 RO Uni NC PT
RW Read / Write RO Read only Uni Unipolar Bi Bi-polar Bit Bit parameter Txt Text string
FI Filtered DE Destination NC Not copied RA Rating dependent PT Protected US User save PS Power down save