4. Commissioning
4−25
Festo P.BE−CPX−CMAX−SYS−EN en 0908NH
2. Step: Specify record number
Control bytes (step 2)
Bit B7 B6 B5 B4 B3 B2 B1 B0
CCON
OPM2 OPM1 LOCK RESET BRAKE ST OP ENAB L E
Byte 1
0 0 0 0 0 1/0 1 1
CPOS
CLEAR TEACH JOGN JOGP HOM ST ART HOLD
Byte 2
0 0 0 0 0 0 0 0
Record no . Record number of the record to be started, example record 36 (0x24):
Byte 3
0 0 1 0 0 1 0 0
res. Byte 4 ... 8: reserved (= 0)
No change in the status bytes:
Status bytes (step 2)
Bit B7 B6 B5 B4 B3 B2 B1 B0
SCON
OPM2 OPM1 FCT_MMI 24VL FAUL T WARN OPEN EN AB LED
Byte 1
0 0 0 1 0 0 1 1
SPOS
REF STILL DEV MO V TEA CH MC ACK HOLD
Byte 2
1 x x x x x 0 0
Record no . Acknowledgement of last started record.
Byte 3
x x x x x x x x
RSB
XLIM VLIM RCE COM1 RC C RC1
Byte 4
x x x x x x x x
Primary
actual
value
Byte 5 ... 8: Acknowledgement of the actual value of the position or force in the
configured system of units.
After setting the record number, wait at least 1 bus cycle
(recommendation: 1 PLC cycle) so that the record number has
definitely been transmitted to the CMAX before starting.

Table of Contents

Other manuals for Festo CPX-CMAX-C1-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Festo CPX-CMAX-C1-1 and is the answer not in the manual?

Festo CPX-CMAX-C1-1 Specifications

General IconGeneral
BrandFesto
ModelCPX-CMAX-C1-1
CategoryController
LanguageEnglish

Related product manuals