20
3
Parameter functions and setting procedure
3-1  1st block parameter
MANU
 Manual mode selection (001)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to select how to set the manipulated variable, automatically or manually.
Setpoint
Description
oFF
Automatically
oN
Manually
 
MANU indicator lights during manual operation. (see page 11)
 
In this screen, only the switchover between auto/manual is available.  Manual operation of control output is 
available on PV/MV screen.
This parameter is not displayed in default setting. To use this parameter, change the 
setting of the parameter “Parameter mask” (see page 68).
[Setting example] Changing the mode from Auto to Manual   –––––––––––––––––
Display Operating procedure
1. 
Press and hold the   key for about one second during the SV/PV display.
 appears.
2. 
Press the   key.
The setpoint starts blinking.
3. 
Press the   or   keys to change “ oFF ” to “ oN .”
4. 
Press the   key or wait for three seconds to save the change.
5. 
Press the   key.
The screen returns to the SV/PV display.