2nd block parameter
SVOF
SV shift (050)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This function species the SV shift. This is used to eliminate remaining offset when using P control.
Setting range
-50.00 to 50.00%FS
Controls act on the calculated SV with SV offset.
Alarm determination acts on the displayed SV without SV offset.
[Setting example] Setting the SV shift to 7°C –––––––––––––––––––––––––––––
Display Operating procedure
1.
Press and hold the key for about three seconds during the SV/PV display.
appears.
2.
Press the key to display .
3.
Press the key.
The setpoint starts blinking.
4.
Press the or keys to change “ 0.0 ” to “ 7.0 .”
5.
Press the key or wait for three seconds to save the change.
6.
Press the key.
The screen returns to the SV/PV display.