47
2nd block parameter
SVOF
 SV shift (050)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This function species the SV shift. This is used to eliminate remaining offset when using P control.
Setting range
-50.00 to 50.00%FS
 
Controls act on the calculated SV with SV offset.
 
Alarm determination acts on the displayed SV without SV offset.
[Setting example] Setting the SV shift to 7°C  –––––––––––––––––––––––––––––
Display Operating procedure
1. 
Press and hold the   key for about three seconds during the SV/PV display.
 appears. 
2. 
Press the   key to display  .
3. 
Press the   key.
The setpoint starts blinking.
4. 
Press the   or   keys to change “ 0.0 ” to “ 7.0 .”
5. 
Press the   key or wait for three seconds to save the change.
6. 
Press the   key.
The screen returns to the SV/PV display.