71
3rd block parameter
FLo1
 MV1 during FALT (146)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to specify the control output value when the controller falls into FALT (input error).
Setting range
-5.0 to 105.0%
[Setting example] Setting the OUT1 during FALT to 5% –––––––––––––––––––––
Display Operating procedure
1. 
Press and hold the   key for about ve seconds during the SV/PV display.
 appears.
2. 
Press the   key to display  .
3. 
Press the   key.
The setpoint starts blinking.
4. 
Press the  ,   or   keys to change “ -5.0 ” to “ 5.0 .”
5. 
Press the   key or wait for three seconds to save the change.
6. 
Press the   key.
The screen returns to the SV/PV display.